Temperature Accuracy Verification
- Place calibrated thermometer near installed sensor
- Allow stabilization for 15–20 minutes
- Compare both readings, calculate deviation
- Acceptable difference: ±0.5°C
- Calibrate or flag for adjustment if deviation exceeds threshold
- Log before and after calibration readings
Humidity Sensor Validation
- Position calibrated hygrometer near the sensor
- Allow 30 minutes stabilization time
- Check deviation from reference (±3% RH acceptable)
- Perform salt chamber test if applicable
- Record readings and note need for recalibration
Alarm Testing Protocol
- Activate test mode for the monitoring system
- Adjust threshold near current value to trigger alarm
- Check for local alarm and remote notification
- Verify alert delivery channels (SMS/email/SNMP)
- Reset to original values and confirm return to normal
Network & Connectivity Test
- Verify IP connectivity via ping command
- Check SNMP/HTTPS communication with server
- Test polling from DCIM/BMS software
- Simulate disconnect to ensure auto-recovery
- Confirm real-time data flow on dashboard