Exit Pathway Light Inspection Checklist

Introduction

Regular inspection of exit pathway lighting is critical for ensuring occupant safety during emergency evacuations. This comprehensive checklist helps facility managers, maintenance personnel, and safety officers identify potential issues with emergency lighting systems before they compromise life safety during power outages, fires, or other emergency situations.

Following this exit pathway light inspection checklist as part of your routine building maintenance program helps maintain reliable emergency egress illumination, ensures compliance with fire and building codes, and provides documentation for regulatory inspections. The checklist aligns with NFPA 101 (Life Safety Code), International Building Code (IBC), and other applicable regulations governing emergency lighting requirements in commercial, institutional, and public buildings.

Code Requirements

Emergency egress lighting is governed by several important codes and standards, including:

  • NFPA 101 (Life Safety Code): Requires minimum illumination of 1 foot-candle (10.8 lux) along the path of egress, with reliability for at least 90 minutes during power failure.
  • International Building Code (IBC): Mandates illumination of means of egress with emergency power backup for specific occupancy types.
  • NFPA 70 (National Electrical Code): Provides requirements for emergency system installation and electrical safety.
  • Local Building Codes: May impose additional or modified requirements based on local jurisdictions.

Equipment Information

Pro Tips for Effective Exit Light Inspection

  • Simulate True Emergency Conditions: When testing battery backup systems, simulate a true power outage by disconnecting normal power rather than just using the test button. This provides a more realistic assessment of emergency performance.
  • Use Light Meters for Verification: Utilize a calibrated light meter (illuminance meter) to objectively measure light levels along egress paths. This ensures compliance with the code-required minimum of 1 foot-candle (10.8 lux) at floor level.
  • Document with Photos: Take date-stamped photographs of exit pathway lights during testing, both in normal operation and during emergency mode. These visual records provide valuable documentation for compliance verification and help track degradation over time.

Physical Condition

Normal Power Operation

Emergency Power Operation

Battery Systems

Illumination Levels

Electrical Connections

Accessibility and Visibility

Exit Signs/Combined Units

Documentation and Labeling

Integration with Fire Alarm System

Detailed Inspection Procedures

Follow these structured procedures to ensure a thorough inspection of exit pathway lights. Adapt these steps to your specific lighting system and facility requirements.

Visual Inspection Process

  • Check physical condition of light housing and mounting
  • Examine lenses for cracks, discoloration, or fogging
  • Verify proper aim of light heads toward egress path
  • Check for signs of water damage or corrosion
  • Inspect electrical connections without disassembly
  • Record any physical damage or deterioration
  • Verify installation matches building plans

Functional Test Procedure

  • Verify normal operation on building power
  • Press test button to initiate short functional test
  • Check immediate illumination of all lamps
  • Listen for unusual noises during operation
  • Verify indicator lights show proper status
  • Allow system to automatically return to normal
  • Document response time and any anomalies

90-Minute Duration Test

  • Schedule test during minimal building occupancy
  • Notify building occupants before testing
  • Disconnect normal power supply or use test switch
  • Record start time of test
  • Check light output at beginning, middle, and end of test
  • Measure illumination levels with light meter
  • Document performance throughout 90-minute duration
  • Verify proper return to normal operation
  • Allow adequate time for battery recharging after test

Battery System Inspection

  • Check battery manufacturing date
  • Inspect battery connections for tightness
  • Look for signs of corrosion on terminals
  • Inspect for electrolyte leakage (wet cell batteries)
  • Verify charging system operation
  • Measure battery voltage if accessible
  • Document battery condition
  • Determine if replacement is needed based on age/condition

Inspection Progress

0% complete

Electronic Signature

Apply Signature

Deficiencies & Corrective Actions

Inspection and Testing Guidelines

These guidelines outline recommended inspection and testing frequencies for exit pathway lighting based on NFPA 101 (Life Safety Code) and industry best practices. Following these schedules helps ensure system reliability and compliance with regulatory requirements.

Monthly Inspection

  • Visual inspection of physical condition
  • Brief functional test using test button (minimum 30 seconds)
  • Verification of indicator lights and charging status
  • Check for obvious damage or obstructions
  • Ensure accessibility of light fixtures
  • Document inspection in facility log

Annual Inspection

  • All monthly inspection items
  • Full 90-minute duration test
  • Light meter verification of illumination levels
  • Battery system thorough inspection
  • Cleaning of fixtures and lenses
  • Detailed electrical connection inspection
  • Update of inspection tags/labels
  • Comprehensive documentation of test results

Three-Year Testing

  • All annual inspection items
  • Complete system diagnostic testing
  • Verification of compliance with current codes
  • Assessment of system for upgrade requirements
  • Third-party certification (if required)
  • Complete documentation review
  • Assessment of battery replacement needs

Immediate Attention Required For

  • Non-functioning lamps or LEDs
  • Failure to illuminate in emergency mode
  • Damaged housing or mounting
  • Batteries not holding charge
  • Exit signs not clearly visible
  • Insufficient illumination along egress path
  • New obstructions blocking light coverage
  • Signs of electrical hazards or overheating

Conclusion

Implementing this comprehensive Exit Pathway Light Inspection Checklist is essential for maintaining reliable emergency lighting for safe building evacuation. By systematically inspecting these critical life safety systems, facility managers can ensure proper function during emergencies while maintaining compliance with building codes and safety regulations.

For optimal inspection management, consider implementing the Oxmaint platform to streamline your emergency lighting inspections. The Oxmaint software allows digital documentation of inspections, provides real-time alerts for maintenance requirements, and creates comprehensive historical records for each component of your emergency lighting system. With the Oxmaint APP, facility managers can easily track compliance, monitor maintenance patterns, and ensure all emergency lighting equipment is properly inspected and maintained.

Make exit pathway light inspections an integral part of your facility safety program with Oxmaint's comprehensive inspection management solution. Whether for regulatory compliance, insurance requirements, or occupant safety, this digital approach significantly improves inspection thoroughness and documentation while reducing administrative burden on maintenance personnel.